Master Industrial
DC BUS 220 Vdc
Ideal for industrial installations
Master Industrial series UPS provide maximum protection and power quality for any type of load, especially industrial applications, such as manufacturing
and petrochemical processes, electrical distribution and power plants. Master Industrial is an on-line double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with input and output isolation transformers.
Industrial environment
Master Industrial is suited to the most demanding installation environments where there are vibrations, mechanical stresses, dust and in general where operating conditions are unfavourable to products created for the standard UPS market.
High ICC
The high short-circuit current (ICC = 3) makes it suitable for loads that require high current peaks during switch-on or during normal operation.
Continuous voltage 220 V
The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 elements), the standard industrial value.
Redundant ventilation
Redundant ventilation at 100% load is standard, ensuring operation with a normal load with half of the fans operating; in addition, each fan is monitored and an alarm signal is provided in the event of failure.
The Easy Source input features, the Battery Care System, and the flexibility and communications capabilities are the same as those of the conventional Master MPS range.
Isolation transformer
Synchronisation device (UGS)
Hot connection device (PSJ)
Generator interface
Parallel configuration kit (Closed Loop)
Battery cabinets empty or for extended runtimes
Top Cable Entry cabinets
IP rating IP31/IP42
Техническая спецификация
Models | MIM 80 |
---|---|
INPUT | |
Rated power | 80000 VA |
Voltage | 400 Vac three-phase Vac |
Voltage tolerance | ± 20% |
Frequency | 50/60 Hz with autorange |
Frequency tolerance | 45/65 Hz |
Power factor | 0.93 |
Current distorsion | <5% |
Soft start | 0-100% in 10" |
BY PASS | |
Rated voltage | 400 Vac three-phase selectable 380 and 415 |
Voltage tolerance | ± 15% (selectable from ± 10% to ± 25% from front panel) |
Rated frequency | 50/60 Hz (autorange) |
Frequency tolerance | ± 2% (selectable from ± 1% to ± 5% from front panel) |
Number phases | 3 |
Back-feed protection | yes |
Overload capacity Inx10ms | 14 |
OUTPUT and INVERTER OUTPUT | |
Rated power | 80000 VA |
Active power | 64000 W |
Number phases | 3 + N |
Crest factor (Ipeak/Irms) | 3 : 1 |
Waveform | Sinewave |
Static stability | ± 1% |
Dynamic stability | ± 5% in 5 ms |
Frequency | same as the input (autorange) |
Voltage distortion with distorcing load | <3% |
Voltage distortion with linear load | 1% (rated) 2% (max) |
Frequency stability | ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present |
Inverter efficiency at rated load | 95% % |
Overload | 125% 150% 200% of the rated current for 10^ / 1^ / 7§ |
RECTIFIER OUTPUT | |
Ripple | <1% |
BATTERIES | |
Type | Maintenance-free sealed lead-acid |
Maximum recharge current | 0.2xC10 |
ENVIRONMENTAL | |
Altitude max | 1000 m |
Color | Light grey RAL 7035 |
Remote controls | EPO and bypass |
Safety compliance | EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU |
EMC conformance | EN 62040-2 and Directive 2014/30/EU |
Protection rating | 3 |
Cooling (type) | redundant fans |
AC/AC efficiency | 92,5% |
Noise | 63 dBA at 1 m |
Remote signals | voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA) |
Operating temperature | 0 ÷ 40 °C |
Relative humidity | 95% no condensing |
DATA | |
Weight | 1500 Kg |
Dimensions (h w d) | 1900x1600x800 mm |