^Наверх
Написать нам
Ваше имя* E-mail* Телефон Сообщение* Введите текст на картинке *
+7 (495) 011 04 79 Обратный звонок
14

Master Industrial

Фильтр
ТЕХНОЛОГИИ:
ОБЛАСТИ ПРИМЕНЕНИЯ:
  

Power Range: 30 - 80 kVA

DC BUS 220 Vdc
Ideal for industrial installations

Master Industrial series UPS provide maximum protection and power quality for any type of load, especially industrial applications, such as manufacturing
and petrochemical processes, electrical distribution and power plants. Master Industrial is an on-line double conversion UPS (class VFI SS 111 in accordance with IEC EN 62040-3) with input and output isolation transformers.
Технические характеристики

Industrial environment
Master Industrial is suited to the most demanding installation environments where there are vibrations, mechanical stresses, dust and in general where operating conditions are unfavourable to products created for the standard UPS market.

High ICC
The high short-circuit current (ICC = 3) makes it suitable for loads that require high current peaks during switch-on or during normal operation.

Continuous voltage 220 V
The input and inverter transformers guarantee the isolation of the batteries, which are sized for a voltage of 220 Vdc (from 108 to 114 elements), the standard industrial value.

Redundant ventilation
Redundant ventilation at 100% load is standard, ensuring operation with a normal load with half of the fans operating; in addition, each fan is monitored and an alarm signal is provided in the event of failure.
The Easy Source input features, the Battery Care System, and the flexibility and communications capabilities are the same as those of the conventional Master MPS range.

Isolation transformer
Synchronisation device (UGS)
Hot connection device (PSJ)
Generator interface
Parallel configuration kit (Closed Loop)
Battery cabinets empty or for extended runtimes
Top Cable Entry cabinets
IP rating IP31/IP42

Техническая спецификация


Models MIM 80
INPUT
Rated power 80000 VA
Voltage 400 Vac three-phase Vac
Voltage tolerance ± 20%
Frequency 50/60 Hz with autorange
Frequency tolerance 45/65 Hz
Power factor 0.93
Current distorsion <5%
Soft start 0-100% in 10"
BY PASS
Rated voltage 400 Vac three-phase selectable 380 and 415
Voltage tolerance ± 15% (selectable from ± 10% to ± 25% from front panel)
Rated frequency 50/60 Hz (autorange)
Frequency tolerance ± 2% (selectable from ± 1% to ± 5% from front panel)
Number phases 3
Back-feed protection yes
Overload capacity Inx10ms 14
OUTPUT and INVERTER OUTPUT
Rated power 80000 VA
Active power 64000 W
Number phases 3 + N
Crest factor (Ipeak/Irms) 3 : 1
Waveform Sinewave
Static stability ± 1%
Dynamic stability ± 5% in 5 ms
Frequency same as the input (autorange)
Voltage distortion with distorcing load <3%
Voltage distortion with linear load 1% (rated) 2% (max)
Frequency stability ± 0,05% on mains failure ± 2% (selectable from ± 1% to ± 5% from front panel) with mains supply present
Inverter efficiency at rated load 95% %
Overload 125% 150% 200% of the rated current for 10^ / 1^ / 7§
RECTIFIER OUTPUT
Ripple <1%
BATTERIES
Type Maintenance-free sealed lead-acid
Maximum recharge current 0.2xC10
ENVIRONMENTAL
Altitude max 1000 m
Color Light grey RAL 7035
Remote controls EPO and bypass
Safety compliance EN 62040-1:2008; EN 62040-1/EC:2009; EN 62040-1/A1:2013 and Directive 2014/35/EU
EMC conformance EN 62040-2 and Directive 2014/30/EU
Protection rating 3
Cooling (type) redundant fans
AC/AC efficiency 92,5%
Noise 63 dBA at 1 m
Remote signals voltage free contacts (mains power failure, UPS on bypass, end of discharge pre-alarm, output 12Vdc 80mA)
Operating temperature 0 ÷ 40 °C
Relative humidity 95% no condensing
DATA
Weight 1500 Kg
Dimensions (h w d) 1900x1600x800 mm